ReFlex Power™ Programming Manual DC Module Remote Programming
64 M380056-03 Rev M
3.10
INPUT SCPI COMMANDS
3.10.1 INPUT
SCPI
C
OMMAND
S
UMMARY
INPut<n>
:MENAble:MODE <NRi>
:MENAble:MODE?
:STATE?
3.10.2
INPUT
SCPI
C
OMMAND
R
EFERENCE
Command
Description
INPut<n>
:MENAble:MODE <NRi>
0 = Allows the Module ENAble signal to turn the DC supply back On,
only if it was faulted off by Module ENAble going false. (Default
setting) If the supply was off by Module ENAble, and a *RST<n> is
issued, the DC supply will not turn on, unless a OUTP<n>:STAT 1
command is issued.
1 = Prevents the Module ENAble signal from turning the DC supply
On. An OUTP:STAT 1 is required to turn the supply back on.
2 = Module ENAble will always try to turn on the DC supply when it
goes from Off to On. Note: Settings are automatically saved.
:MENAble:MODE?
Query the Module ENAble MODE setting. Default is 0.
:MENAble:STATE?
1 = The Hardware Module ENAble signal is asserted, the module can
be turned On.
0 = When the Hardware Module ENAble is false; the module is Off.
Note: The usage of the OUTPut<n>:MODFault On
command will temporarily disable
the operation of the INPut<n>:MENA:MODE
command while it’s active.